Installation precautions for Y Type Strainer

FONT

Feb 21,2023

Y Type Strainer is a filter device for the pipeline system of conveying medium. Y Type Strainer is usually installed at the inlet of pressure reducing valve, pressure relief valve, fixed water level valve or other equipment to remove impurities in the medium to protect Normal use of valves and equipment. The filter is suitable for liquid and gas materials in the production of chemical industry, petrochemical industry, light industry, etc., and is used to filter its solid impurities.

Y Type Strainer
Notes on Y Type Strainer installation:
1. The installation of Y Type Strainer should be carried out according to the flow direction, recommended installation method and installation requirements shown in the product catalog and installation instructions provided by the manufacturer.
2. The upstream and downstream of the Y Type Strainer can be equipped with differential pressure gauges or pressure gauges according to the needs of process production to judge the clogging situation, and the backflush cleaning pipeline should be configured according to the process needs.
3. The convenience of installation and removal of permanent and temporary Y Type Strainers should be considered when piping.
4. Pipeline Y Type Strainer has requirements for pipeline design.
5. The pipeline equipped with Y Type Strainer can be divided into intermittent operation and continuous operation when working.
6. During intermittent operation, set shut-off valves before and after the Y Type Strainer to clean the Y Type Strainer.
7. For continuous operation, two sets of Y Type Strainers connected in parallel shall be installed for the permanent Y Type Strainer, and cut-off valves shall be set before and after the Y Type Strainer (except for line gap filters).
In addition to the above 7 points, when installing a large-diameter socket welding Y Type Strainer, pay attention to whether this type of Y Type Strainer gasket is made of non-metallic material. If it is made of non-metallic material, it is easy to cause damage due to overheating, so when welding After the completion, the Y Type Strainer should be cooled quickly to reduce the welding time.

Key words: Y,Type,Strainer